Remko WPM-Smart-Control-Manual for specialists-WKF-085 Manuel d'utilisateur Page 1

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Matériel Remko WPM-Smart-Control-Manual for specialists-WKF-085. REMKO WPM-Smart-Control-Manual for specialists-WKF-085 User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 84
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Operating manual
Read the instructions prior to performing any task!
REMKO Smart WP MANAGER
Smart-Control for WKF/WKF-compact 85/120/180
Manual for experienced specialists
0032-2012-09 Edition 1, en_GB
Vue de la page 0
1 2 3 4 5 6 ... 83 84

Résumé du contenu

Page 1 - Operating manual

Operating manualRead the instructions prior to performing any task!REMKO Smart WP MANAGERSmart-Control for WKF/WKF-compact 85/120/180Manual for experi

Page 2 - Made by REMKO

3 Operation - User level 3.1 Menu structure of the con-troller The following information is primarily directed atsystem operators. Specialists

Page 3 - Table of contents

Overview of the menus (User level)LEVEL 03D houseHot waterRoom climateLEVEL 1Information Settings MessagesLEVEL 2BasicinformationSolarBasicsettingsSol

Page 4

"3D house" animationOnce the Smart-Control commissioning wizard hasbeen completed, you will see the home screen withthe 3D house. Pressing t

Page 5

Explanation of operating modes:Standby - the controller waits for the next requestDispensing operation - hot water is being dis-pensedCirculation - ci

Page 6

Favourites menu: for the userUsing the rotary knob (turning it clockwise) you canaccess other views. They allow you to rapidly andeasily adjust the mo

Page 7 - Operation - General

One-off hot water / party modeActivating Party mode (select with the rightsoftkey) causes the next window of time withreduced heating to be disregarde

Page 8

CO2 savingsCO2 savings specifies how much CO2 emissionshave been avoided. The calculation of CO2 savingsis based on the amount of renewable energy gen

Page 9 - Next viewStart animation

"Information" menu item - UserThis menu contains information about the current operating status of the system. The menu is opened withthe

Page 10 - REMKO Smart WP MANAGER

"Information" menu item (continued) - UserAuthorisa-tion levelLevel 2menu itemLevel 3 menu item InfoSolarPump A01 / Pump control signal A4

Page 11 - Aditional

"Information" menu item (continued) - UserAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item InfoFloorheating cycleAbs.prim. pump speed

Page 12

Made by REMKOTranslation of the original operating manualRead these operating instructions carefully before commis-sioning / using this device!These

Page 13

"Information" menu item (continued) - UserAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item InfoHeat pumpHeat pump statusYou can findm

Page 14

"Settings" menu item - UserIn this menu you can configure the settings. For example, you can adjust hot water and heating tempera-tures or

Page 15 - Time period

"Settings" menu item (continued) - UserAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item Level 4 menu item InfoHeating /coolingModeRoo

Page 16

4 Operation - Expert level 4.1 Commissioning wizard The commissioning wizard which starts when thecontroller is activated is intended for pro

Page 17

Setting the countrySelect the country with the rotary knob and confirmthe entry with "OK".Fig. 30: Selecting a countryMenu item ParameterFac

Page 18

Menu item ParameterFactorysettingNederlandsPolskiPress "Next".Setting the time zone for the winter timeSelecting the time zone for the winte

Page 19

Activating the heat pumpThe controller detects automatically that a heatpump has been connected. If necessary, activatethe heat pump (select with the

Page 20

ReheatingDesired charging temperature for the hot waterstorage tank.Set temperature to which conventional reheatingshould heat the storage tank to ens

Page 21

Circulation type(dependent on which probes are used)Impulse circulation:If briefly dispensing water triggers an impulse onthe flow-operated safety dev

Page 22

Impulse-guided circulation - Disable switch-onAfter the running time of the circulation pump, thepump cannot be started again while disable switchon i

Page 23 - Operation - Expert level

Table of contents1 Safety and usage instructions...

Page 24

Heating-curve heating cycle modeThe heating curve can be adjusted in three points,according to the structure and location-related con-ditions of the b

Page 25

System separationActivation if the floor heating cycle is separated bya heat exchanger.To control a separate heating cycle pump with asystem separatio

Page 26

Standard inlet temperature:the standard inlet temperature corresponds to theset temperature of the heating water at thestandard outside temperature in

Page 27

BuildingtypeHeat retention abilityRecom-mended valueLight Low heat retention ability, e.g. prefab / wood-frame houses approx. 10hMedium Moderate heat

Page 28

Cooling functionActivate (select with the rotary knob and confirmwith "OK") if the building is to be actively cooledwith the heat pump in su

Page 29

Menu item Parameter Factory settingPump type(solar cycle)AsynchronouspumpEC pumpSelectionaccording topump typeinstalled in thesolar cycleSolar speed c

Page 30

Setting the impulse rate of the solar mediumflow rate probeThe impulse rate may only be changed (select withthe rotary knob and confirm with "OK&

Page 31

Set temperature of the storage tank duringsolar chargingOnce the solar set temperature is reached, thesolar cycle pump is switched off. With the colle

Page 32

4.2 Template hydraulic diagrams with installation parameters NOTICE!The following template hydraulic systems are only to be used as a planning aid

Page 33

Menu item Parameter Factory settingControl panel address Control panel 1-3 Control panel 1Country Deutschland - Slovensko DeutschlandLoad setting Acce

Page 34

1 Safety and usageinstructions 1.1 General safety notes Carefully read the operating manual before com-missioning the units for the first time.

Page 35

Menu item Parameter Factory settingCooling function Activated / Deactivated Deactivated / Enable as requiredSeparate cooling cycle Activated / Deactiv

Page 36

Hydraulic diagram for heat pump assembly WKF FrankfurtFunctions: heating and hot water, operating mode: monoenergetic or bivalent alternative. Solar p

Page 37

Menu item Parameter Factory settingCirculation running time 1 min - 15 mins 5 minsDisable switch-on 1 min - 15 mins 5 minsCirculation type Impulse or

Page 38

Hydraulic diagram for heat pump assembly WKF Dortmund 2Functions: heating or cooling and hot water, operating mode: monoenergetic.Only one cycle is po

Page 39

Menu item Parameter Factory settingCirculation running time 1 min - 15 mins 5 minsDisable switch-on 1 min - 15 mins 5 minsCirculation type Impulse or

Page 40

Hydraulic diagram for heat pump assembly WKF compact StuttgartFunctions: heating or cooling and hot water, operating mode: monoenergetic.Only one cycl

Page 41

Menu item Parameter Factory settingCirculation type Impulse or Temperature ImpulseCirculation running time 1 min - 15 mins 5 minsDisable switch-on 1 m

Page 42

Hydraulic diagram for heat pump assembly WKF compact Mannheim bivalentFunctions: heating or cooling and hot water, operating mode: monoenergetic or bi

Page 43

Menu item Parameter Factory settingCirculation type Impulse or Temperature ImpulseCirculation running time 1 min - 15 mins 5 minsDisable switch-on 1 m

Page 44

Hydraulic diagram for heat pump assembly WKF Düsseldorf 2Functions: heating or cooling and hot water, operating mode: monoenergetic.Only one cycle is

Page 45

1.6 Safety notes for the operator The operational safety of the units and compo-nents is only assured providing they are used asintended and in a f

Page 46

Menu item Parameter Factory settingCirculation running time 1 min - 15 mins 5 minsDisable switch-on 1 min - 15 mins 5 minsCirculation type Impulse or

Page 47

Hydraulic diagram for heat pump assembly WKF compact Stuttgart SolarFunctions: heating or cooling/hot water and solar, operating mode: monoenergeticOn

Page 48

Menu item Parameter Factory settingCirculation running time 1 min - 15 mins 5 minsDisable switch-on 1 min - 15 mins 5 minsCirculation type Impulse or

Page 49

Hydraulic diagram for heat pump assembly WKF Frankfurt SolarFunctions: heating/hot water and solar, operating mode: monoenergetic or bivalent possible

Page 50

Menu item Parameter Factory settingCirculation running time 1 min - 15 mins 5 minsDisable switch-on 1 min - 15 mins 5 minsCirculation type Impulse or

Page 51 - FBKKKW WW

4.3 Menu structure of the controller "Information" menu item - ExpertThis menu contains information about the current operating status

Page 52

"Information" menu item (continued) - ExpertAuthorisa-tion levelLevel 2menu itemLevel 3 menu item InfoSolarPump A01 / Pump control signal

Page 53

"Information" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item InfoFloorheating cycleAbs.prim. pump spe

Page 54

"Information" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item InfoHeat pumpHeat pump statusYou can fin

Page 55

"Information" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item Level 4 menu item InfoMeter read-ingsSol

Page 56

1.11 Transport and packaging The devices are supplied in a sturdy shipping con-tainer or inside the heat pump casing. Pleasecheck the equipment imm

Page 57

"Information" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item Level 4 menu item InfoMeter read-ingsHou

Page 58

"Information" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item InfoChecklistCollector temp. S01You can

Page 59

"Settings" menu item - ExpertIn this menu you can configure the settings. For example, you can adjust hot water and heating tempera-tures

Page 60

"Settings" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item Level 4 menu item InfoBasic settings System

Page 61

"Settings" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item Level 4 menu item InfoSolarCollectorMax. te

Page 62

"Settings" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item Level 4 menu item InfoHot waterDomestic wat

Page 63

"Settings" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item Level 4 menu item InfoHeating /coolingBuild

Page 64

"Settings" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item InfoSolar heatingMin. pump speedYou can fin

Page 65

"Settings" menu item (continued) - ExpertAuthorisa-tion levelLevel 2 menuitemLevel 3 menu item Level 4 menu item InfoHeat pumpBasic settin

Page 66

"Messages" menu item - ExpertPressing "OK" (right softkey) takes you to submenus of the menu item "Messages".This is w

Page 67

2 Operation - General 2.1 Design and functions Overview of the controls34546712 2Fig. 1: Controls of the Smart-Control1: SD card2: Movement

Page 68

"Message" menu item (continued) - ExpertManual mode (relay test) (continued) Parameter Selection parameter Cooling changeover valve Ou

Page 69

"Message" menu item (continued) - ExpertManual mode (relay test) (continued) Parameter Selection parameter Panel heating cycle pump st

Page 70

"Message" menu item (continued) - ExpertManual mode (probes) (continued) Parameter Selection parameter Circulation paddle switch Probe

Page 71

"Message" menu item (continued) - ExpertManual mode (probes) (continued) Parameter Selection parameter Solar cycle return temp. Probe

Page 72

5 Installation 5.1 Room installation of theSmart-Control NOTICE!Only use the unit in dry areas and protect itfrom electromagnetic radiation.The

Page 73

6 Electrical wiring 6.1 Structure electrical connection I/0 module Cable cross-sections corresponding to the supplied connection cable!Place the

Page 74

6.2 Terminal assignment / legend Terminal assignmentTerminal Input Output Signal Connection layoutPW X Power supply I/O 230VPP X Power supp

Page 75 - Electrical wiring

Terminal Input Output Signal Connection layoutA11 X Changeover valve 2. heat generatorA12 X Changeover valve solar / 2. storage tank poolA13

Page 76

7 PV power utilisation 7.1 Higher energy consumptionfrom the combination of heatpump and PV plant Ideal for new and existing photovoltaic plants

Page 77

7.2 Using the PV power surplus The self-generated photovoltaic power is used inthe first instance for power needs in the home(lighting, household a

Page 78

Navigation and changing parametersCalling up the main menuPress the menu key until the menu items "Informa-tion", "Settings" and &

Page 79 - Using the PV power surplus

7.3 Systems with aphotovoltaic plant SystemsThe smart heating function can be used with thefollowing variants:n Hybrid heat pumpn Split air/water h

Page 80

8 Index CChanging parameters... 8Connection of the controller to the electricitymeters and inverter...

Page 81

REMKO Smart WP MANAGER 82

Page 83

ConsultingThanks to intensive training, our consultants are always completely up-to-date in terms of technical knowledge. This has given us the reputa

Page 84 - REMKO INTERNATIONAL

Select "Change" (right softkey). The select valueappears marked in blue.Language / TimeTime: 14 : 54Cancel2/7NextFig. 9: Selecting a parame

Commentaires sur ces manuels

Pas de commentaire